Applies in Germany. This page explains the German rules in English. German terms are given in brackets.

How often do fire doors and hold-open devices need checking?

Fire and smoke doors and fire shutters have to close on their own if there is a fire. If they are kept open during the day, a hold-open system (Feststellanlage) is needed: a magnet holds the door open, a smoke detector triggers, and the door swings shut. Regular checks are required so that this works when it counts.

In short

In Germany, fire doors and shutters are checked regularly as set out in their approval or test certificate (workplace rule ASR A1.7, no. 10.2). For hold-open systems this means a function test by the operator at least once a month, and an inspection and service by a qualified technician at least once a year. An acceptance test is required after installation.

Overview for guidance only, not legal advice. No guarantee of accuracy. Intervals and scope depend on design, use and the risk assessment (Gefährdungsbeurteilung). Responsibility lies with the operator.

Check intervals at a glance

Acceptance test of the hold-open system after installationbefore first usethe manufacturer’s technician, a technician authorised by the manufacturer, or a test body named by the DIBt
Function test of the hold-open system: trigger it, the door must close on its ownat least monthly; quarterly after 12 months without defects, if the approval allows ita trained member of the operator’s staff
Inspection and service of the hold-open systemat least once a yearqualified hold-open system technician
The fire door or shutter itself: closing, seals, hardwareas set out in the approval or test certificate and the manufacturer’s instructionscompetent person or specialist firm
What counts is always the approval for the specific system. Employers also set the type, scope and intervals of checks in their risk assessment (Gefährdungsbeurteilung, § 3 ArbStättV). State law may require further checks.

What needs to be recorded?

The scope, result and date of every check are recorded and kept by the operator. In practice, for each door: location or door number, type, approval number, date, result, defects and how they were put right, and who carried out the check.

Frequently asked questions

Can I wedge a fire door open?

No. A fire door may only be held open by an approved hold-open system. A wedge, hook or cable tie stops the door from closing in a fire.

Who may service hold-open systems?

A qualified hold-open system technician, as defined in the German standard DIN 14677-2. The monthly function test can be done by a trained member of the operator’s staff.

What happens during the function test?

The smoke detector or manual call point is triggered, the holding magnet releases the door, and the door has to close fully on its own and latch.

Does this apply to fire shutters too?

Yes. Fire and smoke shutters with a hold-open system are checked in the same way. If they are power-operated, the annual gate inspection under ASR A1.7 applies as well.

Legal basis: German workplace rule ASR A1.7 “Türen und Tore”, no. 10.2 (3); general type approvals (allgemeine Bauartgenehmigungen) of the DIBt for hold-open systems (section on use and maintenance); DIN 14677-1/-2; § 3 ArbStättV. As of November 2026.